²úÆ·ÃèÊö  :  4ϵÁгߴç¿ÉȼÆøÌå´«¸ÐÆ÷£¬¿ÉÓëÓж¾´«¸ÐÆ÷¹²Í¬Ê¹ÓᣠÐÔÄÜÎȶ¨ ²âÁ¿Á¿³Ì£º0£­100%LEL

Combustible Gas Sensor 0 – 100% LEL

Performance Characteristics

Part Number CLL-6012-400

Gas Detected Most combustible gases and vapors

Nominal Range 0-100%LEL

Sensitivity Range 357 mV/%CH4

T90 Response Time < 20 seconds (methane)

Linear to 0-75%LEL

Long Term Sensitivity Drift

<±5%FSS/month

Long Term Zero Drift <±5%LELmethane/month

Warranty Period 12 months

Operation Conditions

Temperature Range -20oC to 50oC

Operating Humidity 15-90%RH non-condensing

Operating Voltage 4.25V D.C.

Operating Current 75±8 mA

Storage no Si,Pb, Sn and S etc.vapors allowed


Excellent long term stability

Excellent H2S poison resistance

Relative Sensitivity

Gas/Vapor

LEL (%vol)

Relative Sensitivity

Methane

5.0

100

Propane

2.1

63

n-Butane

1.9

63

n-Pentane

1.5

48

n-Hexane

1.1

40

n-Octane

1.0

34

Gasoline

1.3

42

Hydrogen

4.0

83

Acetone

2.5

59

Ethanol

3.3

59

m-Xylene

1.1

29

Tolune

1.1

33

Benzene

1.2

43

Styrene

1.1

29

Note: Relative Sensitivities are listed for guidance only. Calibration must be made using the gas under investigation for most accurate consideration.

Temperature Dependence

Product Approval

· UL

Class I, Division I, Groups A, B, C & D Hazardous Locations

Certificate No: E187829

· ATEX(94/9/EC)

II 2G Ex d IIC

Certificate No: DEMKO 03 ATEX 0311958U

Certificate No: 03 ATEX 0311958U

· IECEx

Ex d IIC

Certificate No: IECEx UL 07.0001U

Ex ia IIC T4 Ga or Ex ia I Ma

Certificate No: IECEx KEM 08.0030U

Notes:

1. All performance specifications are based upon the following environment conditions: 20 ¡æ, 50% relative humidity and 1 atmospheric pressure (100 kPa or ambient pressure).

2. Recommend calibration with target gas. If calibration with a cross sensitivity gas, we cannot ensure the accuracy of calibration and measurement.

3. The cross sensitivity may fluctuate between +/- 30% and may differ from batch to batch or from sensor’s life time.

4. The cross sensitivities are including but not limited to the above gases. It may also respond to other gases.

Ïà¹Ø²úÆ·


?
ÔÚÏß¿Í·þ
  • ¹¤Òµ°²È«µã»÷ÕâÀï¸øÎÒ·¢ÏûÏ¢
  • ´óÆø»·±£µã»÷ÕâÀï¸øÎÒ·¢ÏûÏ¢
  • Ò½ÁÆÎÀÉúµã»÷ÕâÀï¸øÎÒ·¢ÏûÏ¢
  • ÐÂÄÜÔ´µã»÷ÕâÀï¸øÎÒ·¢ÏûÏ¢
  • ʯÓÍ»¯¹¤µã»÷ÕâÀï¸øÎÒ·¢ÏûÏ¢
  • ¸ßУ¿ÆÑеã»÷ÕâÀï¸øÎÒ·¢ÏûÏ¢
  • ´«¸ÐÆ÷µã»÷ÕâÀï¸øÎÒ·¢ÏûÏ¢
  • ¼¼ÊõÖ§³Öµã»÷ÕâÀï¸øÎÒ·¢ÏûÏ¢
ÈÈÏߵ绰

0755-85299999

·µ»Ø¶¥²¿

ÔÁICP±¸13055555ºÅ-1 ÔÁ¹«Íø°²±¸44030702008888ºÅ ? Copyright 2018 ÉîÛÚÊнðɳ¼¯ÍÅ186cc(Öйú)ÓÐÏÞ¹«Ë¾µç×ӿƼ¼ÓÐÏÞ¹«Ë¾ All Rights Reserve

¡¾ÍøÕ¾µØͼ¡¿¡¾sitemap¡¿
0.0370s